$********************************************************** $ (c) 2007 $ $ EDS File for Flowserve Limitorque $********************************************************** [File] $ File Description Section: $ For more information about the meaning of each entry, please check $ CIP Networks Library Volume 1 Chapter 7-3.6.1 $ $ Revision 1.3 - $ Changed MinRev to match device = 2 $ $ Revision 1.2 - $ changes to last version: $ incremented revision $ commented out Param82, Param84 (not supported in Autobaud Mode) $ fixed data size of Param19 $ changed descriptor of params (+ enumerated string) $ added connection object attributes for input and output $ extended enumerated string section $ extended parameter groups section $ changed MaxInst value of paramclass section $ changed Output1 parameter size to 9 $ commented out members 82, 85 in Group3 (not supported in Autobaud Mode) DescText = "DeviceNet Limitorque Interface"; CreateDate = 08-24-2005; CreateTime = 12:00:00; ModDate = 05-10-2007; ModTime = 01:08:02; Revision = 1.3; $ HomeURL = ""; [Device] $ Device Description Section: $ For more information about the meaning of each entry, please check $ CIP Networks Library Volume 1 Chapter 7-3.6.2 and CIP Networks Library $ Volume 3 Chapter 7-4 VendCode = 966; $ Identity Object - Vendor ID ProdType = 0; $ Identity Object - Device Type ProdCode = 19800; $ Identity Object - Product Code MajRev = 1; $ Identity Object - Major Revision MinRev = 2; $ Identity Object - Minor Revision ProdName = "Flowserve MX"; $ Identity Object - Product Name VendName = "Flowserve Corporation"; ProdTypeStr = "Generic Device"; Catalog = ""; $ Icon = "Limitorque.ico"; $ Uncomment when HomeURL has been added [Device Classification] $ Device Classification Section: $ For more information about the meaning of each entry, please check $ CIP Networks Library Volume 1 Chapter 7-3.6.3 and CIP Networks Library $ Volume 3 Chapter 7-5 Class1 = DeviceNet; [IO_Info] $ I/O Characteristics Section: $ For more information about the meaning of each entry, please check $ CIP Networks Library Volume 3 Chapter 7-6 Default=0x0001; $ default is Poll Only PollInfo= 0x0007, $ compatible with all 1, $ Default Input = Input1 1; $ Default Output = Output1 StrobeInfo= 0x0007, $ compatible with all 3, $ Default Input = Input3 6; $ Default Output = Output6 COSInfo= 0x0007, $ compatible with all 5, $ Default Input = Input5 1; $ Default Output = Output1 $ Input Connections $ For more information about the encoding of the Connection Path format $ please check CIP Networks Library Volume 1 Appendix C-1 Input1= 16, $ 16 bytes are transfered 0, $ all bits are significant 0x000D, $ Poll and COS/Cyclic "Assembly Instance 105", $ Name 6, "20 04 24 69 30 03", $ Assembly Object Instance 105, Attribute 3 "All Status Information"; $ Help Input2= 6, $ 6 bytes are transfered 0, $ all bits are significant 0x000F, $ Poll, Strobe and COS/Cyclic "Assembly Instance 106", $ Name 6, "20 04 24 6A 30 03", $ Assembly Object Instance 106, Attribute 3 "Position and Faults only"; $ Help Input3= 8, $ 8 bytes are transfered 0, $ all bits are significant 0x000F, $ Poll, Strobe and COS/Cyclic "Assembly Instance 107", $ Name 6, "20 04 24 6B 30 03", $ Assembly Object Instance 107, Attribute 3 "Position, Torque and Faults only"; $ Help Input4= 11, $ 11 bytes are transfered 0, $ all bits are significant 0x000D, $ Poll and COS/Cyclic "Assembly Instance 108", $ Name 6, "20 04 24 6C 30 03", $ Assembly Object Instance 108, Attribute 3 "Pos, Torq, Usr and Faults only"; $ Help Input5= 6, $ 6 bytes are transfered 0, $ all bits are significant 0x000F, $ Poll, Strobe and COS/Cyclic "Assembly Instance 109", $ Name 6, "20 04 24 6D 30 03", $ Assembly Object Instance 109, Attribute 3 "Faults and Alarms only"; $ Help $ Output Connections Output1= 9, $ 9 bytes are transfered 0, $ all bits are significant 0x000D, $ Poll and COS/Cyclic "Assembly Instance 100", $ Name 6, "20 04 24 64 30 03", $ Assembly Object Instance 100, Attribute 3 "All Control Channels"; $ Help Output2= 5, $ 5 bytes are transfered 0, $ all bits are significant 0x000D, $ Poll and COS/Cyclic "Assembly Instance 101", $ Name 6, "20 04 24 65 30 03", $ Assembly Object Instance 101, Attribute 3 "Analog Control and ESD only"; $ Help Output3= 4, $ 4 bytes are transfered 0, $ all bits are significant 0x000D, $ Poll and COS/Cyclic "Assembly Instance 102", $ Name 6, "20 04 24 66 30 03", $ Assembly Object Instance 102, Attribute 3 "Discrete Control and ESD only"; $ Help Output4= 3, $ 3 bytes are transfered 0, $ all bits are significant 0x000D, $ Poll and COS/Cyclic "Assembly Instance 103", $ Name 6, "20 04 24 67 30 03", $ Assembly Object Instance 103, Attribute 3 "Analog Control only"; $ Help Output5= 3, $ 4 bytes are transfered 0, $ all bits are significant 0x000D, $ Poll and COS/Cyclic "Assembly Instance 104", $ Name 6, "20 04 24 68 30 03", $ Assembly Object Instance 104, Attribute 3 "Discrete Control only"; $ Help Output6= 8, $ 8 bytes are transfered (Bit Strobe Command) 1, $ 1 bit is significant 0x0002, $ Strobe "DO_ESD_Bit_Strobe_Cnxn", $ Name 6, "20 64 24 01 30 16", $ Channel Interface Object Instance 1, Attribute 22 "Cmd ESD from Bit-Strobe Cnxn"; $ Help [ParamClass] $ Parameter Class Section: $ For more information about the meaning of each entry, please check $ CIP Networks Library Volume 1 Chapter 7-3.6.4 and Chapter 5-14.1 MaxInst = 87; $ number of parameters supported Descriptor = 0x0003; $ supports parameter instances and full attributes CfgAssembly = 0; $ not used here [Params] $ Parameter Section: $ For more information about the meaning of each entry, please check $ CIP Networks Library Volume 1 Chapter 7-3.6.5 and Chapter 5-14.2 $********************************************************** $ Channel Interface Object Instance Attributes $********************************************************** Param1= 0, $ parameter value slot 6, "20 64 24 01 30 01", $ link path size and path 0x0020, $ descriptor: monitoring 0xC7, 2, $ type is UINT, length is 2 byte "AO_Ctrl_Valve_Flow_Chan", $ parameter name "", $ units string "Desired valve position", $ help string 0, 0xFFFF, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param2= 0, $ parameter value slot 6, "20 64 24 01 30 02", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xD1, 1, $ type is BYTE, length is 1 byte "DI_Position_And_Bus_Mode_Chan", $ parameter name "", $ units string "Valve Status and Control Mode", $ help string 0x21, 0x90, 0x90, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param3= 0, $ parameter value slot 6, "20 64 24 01 30 03", $ link path size and path 0x0032, $ descriptor: monitoring + read only + enumerated string 0xD1, 1, $ type is BYTE, length is 1 byte "DI_Position_Chan", $ parameter name "", $ units string "Valve Status", $ help string 0x00, 0xFF, 0x00, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param4= 0, $ parameter value slot 6, "20 64 24 01 30 04", $ link path size and path 0x0032, $ descriptor: monitoring + read only + enumerated string 0xD1, 1, $ type is BYTE, length is 1 byte "DI_Actuator_Faults_1_Chan", $ parameter name "", $ units string "Mechanical and electrical faults 1", $ help string 0x00, 0xFF, 0x00, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param5= 0, $ parameter value slot 6, "20 64 24 01 30 05", $ link path size and path 0x0032, $ descriptor: monitoring + read only + enumerated string 0xD1, 1, $ type is BYTE, length is 1 byte "DI_Actuator_Faults_2_Chan", $ parameter name "", $ units string "Mechanical and electrical faults 2", $ help string 0x00, 0xFF, 0x00, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param6= 0, $ parameter value slot 6, "20 64 24 01 30 06", $ link path size and path 0x0032, $ descriptor: monitoring + read only + enumerated string 0xD1, 1, $ type is BYTE, length is 1 byte "DI_Actuator_Alarms_Chan", $ parameter name "", $ units string "Emergency shutdown and inhibit information", $ help string 0x00, 0xFF, 0x00, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param7= 0, $ parameter value slot 6, "20 64 24 01 30 07", $ link path size and path 0x0032, $ descriptor: monitoring + read only + enumerated string 0xD1, 1, $ type is BYTE, length is 1 byte "DI_Disc_User_Input_Chan", $ parameter name "", $ units string "Discrete input from user", $ help string 0x00, 0xFF, 0x00, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param8= 0, $ parameter value slot 6, "20 64 24 01 30 08", $ link path size and path 0x0032, $ descriptor: monitoring + read only + enumerated string 0xD1, 1, $ type is BYTE, length is 1 byte "DI_Disc_User_Output_Chan", $ parameter name "", $ units string "Monitor state of relay discrete outputs", $ help string 0x00, 0xFF, 0x00, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param9= 0, $ parameter value slot 6, "20 64 24 01 30 09", $ link path size and path 0x0022, $ descriptor: monitoring + enumerated string 0xC6, 1, $ type is USINT, length is 1 byte "DO_Position_Chan", $ parameter name "", $ units string "Command stop/open/close", $ help string 0, 2, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param10= 0, $ parameter value slot 6, "20 64 24 01 30 0A", $ link path size and path 0x0032, $ descriptor: monitoring + read only + enumerated string 0xC1, 1, $ type is BOOL, length is 1 byte "DO_ESD_Chan", $ parameter name "", $ units string "Command emergency shutdown", $ help string 0x00, 0x01, 0x00, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param11= 0, $ parameter value slot 6, "20 64 24 01 30 0B", $ link path size and path 0x0022, $ descriptor: monitoring + enumerated string 0xD1, 1, $ type is BYTE, length is 1 byte "DO_Relay_Chan", $ parameter name "", $ units string "Command energize relays", $ help string 0x00, 0x7F, 0x00, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param12= 0, $ parameter value slot 6, "20 64 24 01 30 0C", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "AI_Position_Chan", $ parameter name "", $ units string "Current valve position", $ help string 0, 0xFFFF, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param13= 0, $ parameter value slot 6, "20 64 24 01 30 0D", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "AI_Analog_Input_1_Chan", $ parameter name "", $ units string "Value of generic analog input 1", $ help string 0, 0xFFFF, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param14= 0, $ parameter value slot 6, "20 64 24 01 30 0E", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "AI_Analog_Input_2_Chan", $ parameter name "", $ units string "Value of generic analog input 2", $ help string 0, 0xFFFF, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param15= 0, $ parameter value slot 6, "20 64 24 01 30 0F", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "AI_Torque_Chan", $ parameter name "", $ units string "Corrent torque output", $ help string 0, 0xFFFF, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param16= 0, $ parameter value slot 6, "20 64 24 01 30 10", $ link path size and path 0x0032, $ descriptor: monitoring + read only + enumerated string 0xD1, 1, $ type is BYTE, length is 1 byte "DI_Alarms_2_Chan", $ parameter name "", $ units string "Battery and power supply", $ help string 0x00, 0xFF, 0x00, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param17= 0, $ parameter value slot 6, "20 64 24 01 30 11", $ link path size and path 0x0032, $ descriptor: monitoring + read only + enumerated string 0xD1, 1, $ type is BYTE, length is 1 byte "DI_Actuator_Faults_3_Chan", $ parameter name "", $ units string "Mechanical and electrical faults 3", $ help string 0x00, 0xFF, 0x00, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param18= 0, $ parameter value slot 6, "20 64 24 01 30 12", $ link path size and path 0x0020, $ descriptor: monitoring 0xC1, 1, $ type is BOOL, length is 1 byte "DO_Move_Test_Chan", $ parameter name "", $ units string "Move test request", $ help string 0, 1, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param19= 0, $ parameter value slot 6, "20 64 24 01 30 13", $ link path size and path 0x0020, $ descriptor: monitoring 0xC7, 2, $ type is UINT, length is 2 byte "AO_Analog_Output_Chan", $ parameter name "", $ units string "Control of generic analog output", $ help string 0, 0xFFFF, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param20= 0, $ parameter value slot 6, "20 64 24 01 30 14", $ link path size and path 0x0022, $ descriptor: monitoring + enumerated string 0xD1, 1, $ type is BYTE, length is 1 byte "CTRL_Status_Chan", $ parameter name "", $ units string "Set the status associated with the various control values", $ help string 0, 0xFF, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param21= 0, $ parameter value slot 6, "20 64 24 01 30 15", $ link path size and path 0x0020, $ descriptor: monitoring 0xC1, 1, $ type is BOOL, length is 1 byte "DO_ESD_Poll_Cnxn", $ parameter name "", $ units string "Command emergency shutdown from Poll Connection", $ help string 0, 1, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param22= 0, $ parameter value slot 6, "20 64 24 01 30 16", $ link path size and path 0x0020, $ descriptor: monitoring 0xC1, 1, $ type is BOOL, length is 1 byte "DO_ESD_Bit_Strobe_Cnxn", $ parameter name "", $ units string "Command emergency shutdown from Bit-Strobe Connection", $ help string 0, 1, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param23= 0, $ parameter value slot 6, "20 64 24 01 30 17", $ link path size and path 0x0020, $ descriptor: monitoring 0xC1, 1, $ type is BOOL, length is 1 byte "Enable_Broadcast_ESD_Ctrl", $ parameter name "", $ units string "Enab dev to be part of the bcast ESD ctrl scheme from Strobe", $ help string 0, 1, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision $********************************************************** $ Transducer Block Object Instance Attributes $********************************************************** Param24= 0, $ parameter value slot 6, "20 65 24 01 30 01", $ link path size and path 0x0020, $ descriptor: monitoring 0xC7, 2, $ type is UINT, length is 2 byte "Setp_Cutoff_Dec", $ parameter name "", $ units string "When setpoint below defined span, position goes to limit CLOSE", $ help string 0, 1000, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param25= 0, $ parameter value slot 6, "20 65 24 01 30 02", $ link path size and path 0x0020, $ descriptor: monitoring 0xC7, 2, $ type is UINT, length is 2 byte "Setp_Cutoff_Inc", $ parameter name "", $ units string "When setpoint above defined span, position goes to limit OPEN", $ help string 0, 1000, 100, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param26= 0, $ parameter value slot 6, "20 65 24 01 30 03", $ link path size and path 0x0032, $ descriptor: monitoring + read only + enumerated string 0xD2, 2, $ type is WORD, length is 2 byte "Scaled_Values_0", $ parameter name "", $ units string "APT/ATT scaling information", $ help string 0x0000, 0xFFFF, 0x0000, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param27= 0, $ parameter value slot 6, "20 65 24 01 30 04", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xD2, 2, $ type is WORD, length is 2 byte "Scaled_Values_1", $ parameter name "", $ units string "APT Modbus Register 3", $ help string 0x0000, 0xFFFF, 0x0000, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param28= 0, $ parameter value slot 6, "20 65 24 01 30 05", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xD2, 2, $ type is WORD, length is 2 byte "Scaled_Values_2", $ parameter name "", $ units string "APT Modbus Register 4", $ help string 0x0000, 0xFFFF, 0x0000, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param29= 0, $ parameter value slot 6, "20 65 24 01 30 06", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TP_Status_0", $ parameter name "", $ units string "Reserved", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param30= 0, $ parameter value slot 6, "20 65 24 01 30 07", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TP_Status_1", $ parameter name "", $ units string "Start_Position", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param31= 0, $ parameter value slot 6, "20 65 24 01 30 08", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TP_Status_2", $ parameter name "", $ units string "Stop_Position", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param32= 0, $ parameter value slot 6, "20 65 24 01 30 09", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TP_Status_3", $ parameter name "", $ units string "Num_Samples", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param33= 0, $ parameter value slot 6, "20 65 24 01 30 0A", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TP_Status_4", $ parameter name "", $ units string "Max_Torque_Mid", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param34= 0, $ parameter value slot 6, "20 65 24 01 30 0B", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TP_Status_5", $ parameter name "", $ units string "Max_Torque_Position", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param35= 0, $ parameter value slot 6, "20 65 24 01 30 0C", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TP_Status_6", $ parameter name "", $ units string "Avg_Torque", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param36= 0, $ parameter value slot 6, "20 65 24 01 30 0D", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TP_Status_7", $ parameter name "", $ units string "Stop_Torque", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param37= 0, $ parameter value slot 6, "20 65 24 01 30 0E", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TP_Status_8", $ parameter name "", $ units string "Max_Torque_BOT", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param38= 0, $ parameter value slot 6, "20 65 24 01 30 0F", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TP_Status_9", $ parameter name "", $ units string "Max_Torque_EOR", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param39= 0, $ parameter value slot 6, "20 65 24 01 30 10", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_0", $ parameter name "", $ units string "Reserved", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param40= 0, $ parameter value slot 6, "20 65 24 01 30 11", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_1", $ parameter name "", $ units string "MB_TQ_Close_Avg_Last", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param41= 0, $ parameter value slot 6, "20 65 24 01 30 12", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_2", $ parameter name "", $ units string "MB_TQ_Open_Avg_Last", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param42= 0, $ parameter value slot 6, "20 65 24 01 30 13", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_3", $ parameter name "", $ units string "MB_TQ_Open_Peak_Last", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param43= 0, $ parameter value slot 6, "20 65 24 01 30 14", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_4", $ parameter name "", $ units string "MB_TQ_Open_Breakout_Last", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param44= 0, $ parameter value slot 6, "20 65 24 01 30 15", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_5", $ parameter name "", $ units string "MB_TQ_Close_Breakout_Last", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param45= 0, $ parameter value slot 6, "20 65 24 01 30 16", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_6", $ parameter name "", $ units string "MB_TQ_Open_Ending_Last", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param46= 0, $ parameter value slot 6, "20 65 24 01 30 17", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_7", $ parameter name "", $ units string "MB_TQ_Open_Ending_Last", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param47= 0, $ parameter value slot 6, "20 65 24 01 30 18", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_8", $ parameter name "", $ units string "MB_TQ_Close_Peak_Last", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param48= 0, $ parameter value slot 6, "20 65 24 01 30 19", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_9", $ parameter name "", $ units string "MB_TQ_Open_Peak_Ref", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param49= 0, $ parameter value slot 6, "20 65 24 01 30 1A", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_10", $ parameter name "", $ units string "MB_TQ_Open_Breakout_Ref", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param50= 0, $ parameter value slot 6, "20 65 24 01 30 1B", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_11", $ parameter name "", $ units string "MB_TQ_Close_Breakout_Ref", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param51= 0, $ parameter value slot 6, "20 65 24 01 30 1C", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_12", $ parameter name "", $ units string "MB_TQ_Open_Ending_Ref", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param52= 0, $ parameter value slot 6, "20 65 24 01 30 1D", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_13", $ parameter name "", $ units string "MB_TQ_Close_Ending_Ref", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param53= 0, $ parameter value slot 6, "20 65 24 01 30 1E", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "TQ_Status_14", $ parameter name "", $ units string "MB_TQ_Close_Peak_Ref", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param54= 0, $ parameter value slot 6, "20 65 24 01 30 1F", $ link path size and path 0x0020, $ descriptor: monitoring 0xC7, 2, $ type is UINT, length is 2 byte "Travel_Limit_Low", $ parameter name "", $ units string "Lower limit of the valve position in percent of travel span", $ help string 0, 1000, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param55= 0, $ parameter value slot 6, "20 65 24 01 30 20", $ link path size and path 0x0020, $ descriptor: monitoring 0xC7, 2, $ type is UINT, length is 2 byte "Travel_Limit_Up", $ parameter name "", $ units string "Upper limit of the valve position in percent of travel span", $ help string 0, 1000, 100, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param56= 0, $ parameter value slot 6, "20 65 24 01 30 21", $ link path size and path 0x0020, $ descriptor: monitoring 0xDA, 1, $ type is SHORT_STRING, length "Valve_Maint_Date", $ parameter name "", $ units string "Date of last maintanance", $ help string 0,16,"", $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param57= 0, $ parameter value slot 6, "20 65 24 01 30 22", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xDA, 1, $ type is SHORT_STRING, length "Valve_Ser_Num", $ parameter name "", $ units string "Serial num of valve belonging to positioner of electr device", $ help string 0,16,"", $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param58= 0, $ parameter value slot 6, "20 65 24 01 30 23", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xD2, 2, $ type is WORD, length is 2 byte "Valve_Status_0", $ parameter name "", $ units string "Requested relay channel value", $ help string 0x0000, 0xFFFF, 0x0000, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param59= 0, $ parameter value slot 6, "20 65 24 01 30 24", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xD2, 2, $ type is WORD, length is 2 byte "Valve_Status_1", $ parameter name "", $ units string "Status Register - Modbus Register 9", $ help string 0x0000, 0xFFFF, 0x0000, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param60= 0, $ parameter value slot 6, "20 65 24 01 30 25", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xD2, 2, $ type is WORD, length is 2 byte "Valve_Status_2", $ parameter name "", $ units string "Fault Register - Modbus Register 10", $ help string 0x0000, 0xFFFF, 0x0000, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param61= 0, $ parameter value slot 6, "20 65 24 01 30 26", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xD2, 2, $ type is WORD, length is 2 byte "Valve_Status_3", $ parameter name "", $ units string "Digital Output Register - Modbus Register 11", $ help string 0x0000, 0xFFFF, 0x0000, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param62= 0, $ parameter value slot 6, "20 65 24 01 30 27", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xD2, 2, $ type is WORD, length is 2 byte "Valve_Status_4", $ parameter name "", $ units string "Digital Input Register #1 - Modbus Register 12", $ help string 0x0000, 0xFFFF, 0x0000, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param63= 0, $ parameter value slot 6, "20 65 24 01 30 28", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xD2, 2, $ type is WORD, length is 2 byte "Valve_Status_5", $ parameter name "", $ units string "Digital Input Register #2 - Modbus Register 13", $ help string 0x0000, 0xFFFF, 0x0000, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param64= 0, $ parameter value slot 6, "20 65 24 01 30 29", $ link path size and path 0x0032, $ descriptor: monitoring + read only + enumerated string 0xC6, 1, $ type is USINT, length is 1 byte "Valve_Type", $ parameter name "", $ units string "Type of valve", $ help string 0, 2, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param65= 0, $ parameter value slot 6, "20 65 24 01 30 2A", $ link path size and path 0x0032, $ descriptor: monitoring + read only + enumerated string 0xC6, 1, $ type is USINT, length is 1 byte "Actuator_Type", $ parameter name "", $ units string "Type of actuator", $ help string 0, 3, 1, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param66= 0, $ parameter value slot 6, "20 65 24 01 30 2B", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "Diagnostic_Values_0", $ parameter name "", $ units string "Reserved", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param67= 0, $ parameter value slot 6, "20 65 24 01 30 2C", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "Diagnostic_Values_1", $ parameter name "", $ units string "Main Voltage", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param68= 0, $ parameter value slot 6, "20 65 24 01 30 2D", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "Diagnostic_Values_2", $ parameter name "", $ units string "Actuator Position", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param69= 0, $ parameter value slot 6, "20 65 24 01 30 2E", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "Diagnostic_Values_3", $ parameter name "", $ units string "Analog Input #1", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param70= 0, $ parameter value slot 6, "20 65 24 01 30 2F", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC7, 2, $ type is UINT, length is 2 byte "Diagnostic_Values_4", $ parameter name "", $ units string "Analog Input #2", $ help string 0, 65535, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param71= 0, $ parameter value slot 6, "20 65 24 01 30 30", $ link path size and path 0x0020, $ descriptor: monitoring 0xDA, 1, $ type is SHORT_STRING, length "Tag_Name", $ parameter name "", $ units string "Tag name for generic use", $ help string 0,32,"", $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param72= 0, $ parameter value slot 6, "20 65 24 01 30 31", $ link path size and path 0x0022, $ descriptor: monitoring enumerated string 0xC6, 1, $ type is USINT, length is 1 byte "Comm_Loss_Action", $ parameter name "", $ units string "Actuator Action upon detection of communication loss", $ help string 0, 4, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param73= 0, $ parameter value slot 6, "20 65 24 01 30 32", $ link path size and path 0x0020, $ descriptor: monitoring 0xC7, 2, $ type is UINT, length is 2 byte "Comm_Loss_Position", $ parameter name "", $ units string "Position to take upon communication loss", $ help string 0, 1000, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param74= 0, $ parameter value slot 6, "20 65 24 01 30 33", $ link path size and path 0x0020, $ descriptor: monitoring 0xC7, 2, $ type is UINT, length is 2 byte "Comm_Loss_Timeout", $ parameter name "", $ units string "Time to wait after detection comm loss until action is taken", $ help string 0, 1000, 255, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param75= 0, $ parameter value slot 6, "20 65 24 01 30 34", $ link path size and path 0x0020, $ descriptor: monitoring 0xC7, 2, $ type is UINT, length is 2 byte "Deadband", $ parameter name "", $ units string "Deadband percanteage to use when positioning", $ help string 0, 1000, 2, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param76= 0, $ parameter value slot 6, "20 65 24 01 30 35", $ link path size and path 0x0020, $ descriptor: monitoring 0xC7, 2, $ type is UINT, length is 2 byte "Proportional_Band", $ parameter name "", $ units string "Proportional band percanteage to use when positioning", $ help string 0, 1000, 8, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param77= 0, $ parameter value slot 6, "20 65 24 01 30 36", $ link path size and path 0x0020, $ descriptor: monitoring 0xC6, 1, $ type is USINT, length is 1 byte "TQ_Switch_Adjust", $ parameter name "", $ units string "Percentage of full torque to limit operation to", $ help string 0, 100, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param78= 0, $ parameter value slot 6, "20 65 24 01 30 37", $ link path size and path 0x0022, $ descriptor: monitoring + enumerated string 0xC6, 1, $ type is USINT, length is 1 byte "Actuator Control Mode", $ parameter name "", $ units string "Configure actuator for open/close or positioning operation", $ help string 1, 2, 2, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision $********************************************************** $ DeviceNet Object Attributes concerning MAC ID and Baud Rate $********************************************************** Param79= 0, $ parameter value slot 6, "20 03 24 01 30 01", $ link path size and path 0x0020, $ descriptor: monitoring 0xC6, 1, $ type is USINT, length is 1 byte "MAC ID", $ parameter name "", $ units string "Node Address", $ help string 0, 63, 63, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param80= 0, $ parameter value slot 6, "20 03 24 01 30 02", $ link path size and path 0x0022, $ descriptor: monitoring + enumerated string 0xC6, 1, $ type is USINT, length is 1 byte "Baud Rate", $ parameter name "", $ units string "Baud Rate", $ help string 0, 2, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param81= 0, $ parameter value slot 6, "20 03 24 01 30 06", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC1, 1, $ type is BOOL, length is 1 byte "MAC ID Switch Changed", $ parameter name "", $ units string "Node Address Switch has changed sinde last power-up/reset", $ help string 0, 1, 0, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision $ Param82= $ 0, $ parameter value slot $ 6, "20 03 24 01 30 07", $ link path size and path $ 0x0030, $ descriptor: monitoring + read only $ 0xC1, 1, $ type is BOOL, length is 1 byte $ "Baud Rate Switch Changed", $ parameter name $ "", $ units string $ "Baud Rate Switch has changed sinde last power-up/reset", $ help string $ 0, 1, 0, $ min, max, default $ ,,,, $ mult, div, base, offset scaling $ ,,,,0; $ scaling links and precision Param83= 0, $ parameter value slot 6, "20 03 24 01 30 08", $ link path size and path 0x0030, $ descriptor: monitoring + read only 0xC6, 1, $ type is USINT, length is 1 byte "MAC ID Switch Value", $ parameter name "", $ units string "Actual Value of Node Address Switch", $ help string 0, 99, 99, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision $ Param84= $ 0, $ parameter value slot $ 6, "20 03 24 01 30 09", $ link path size and path $ 0x0032, $ descriptor: monitoring + read only + enumerated string $ 0xC6, 1, $ type is USINT, length is 1 byte $ "Baud Rate Switch Value", $ parameter name $ "", $ units string $ "Actual Value of Baud Rate Switch", $ help string $ 0, 9, 9, $ min, max, default $ ,,,, $ mult, div, base, offset scaling $ ,,,,0; $ scaling links and precision Param85= 0, $ parameter value slot 6, "20 03 24 01 30 64", $ link path size and path 0x0022, $ descriptor: monitoring + enumerated string 0xC1, 1, $ type is BOOL, length is 1 byte "Autobaud", $ parameter name "", $ units string "Enable/Disable Autobaud Detection", $ help string 0, 1, 1, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision $********************************************************** $ Connection Object Attributes for Input and Output $********************************************************** Param86= 0, $ parameter value slot 6, "20 05 24 02 30 64", $ link path size and path 0x0022, $ descriptor: monitoring + enumerated string 0xC6, 1, $ type is USINT, length is 1 byte "Polled I/O Input", $ parameter name "", $ units string "Input Assembly Instance used for Polled I/O", $ help string 105, 109, 105, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param87= 0, $ parameter value slot 6, "20 05 24 02 30 65", $ link path size and path 0x0022, $ descriptor: monitoring + enumerated string 0xC6, 1, $ type is USINT, length is 1 byte "Polled I/O Output", $ parameter name "", $ units string "Output Assembly Instance used for Polled I/O", $ help string 100, 104, 100, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param88= 0, $ parameter value slot 6, "20 05 24 03 30 64", $ link path size and path 0x0022, $ descriptor: monitoring + enumerated string 0xC6, 1, $ type is USINT, length is 1 byte "Bit-Strobe I/O Input", $ parameter name "", $ units string "Input Assembly Instance used for Bit-Strobe I/O", $ help string 106, 109, 107, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision Param89= 0, $ parameter value slot 6, "20 05 24 04 30 64", $ link path size and path 0x0022, $ descriptor: monitoring + enumerated string 0xC6, 1, $ type is USINT, length is 1 byte "COS/Cyclic I/O Input", $ parameter name "", $ units string "Input Assembly Instance used for COS/Cyclic I/O", $ help string 105, 109, 109, $ min, max, default ,,,, $ mult, div, base, offset scaling ,,,,0; $ scaling links and precision [EnumPar] $ Parameter Enumerated String Section: $ For more information about the meaning of each entry, please check $ CIP Networks Library Volume 3 Chapter 7-8 Param3= "Opened", "Closed", "Opening", "Closing", "Stop", "Reserved", "Reserved", "Reserved"; Param4= "Monitor Relay", "Valve Jammed", "Manual Moved", "Over Torque", "Phase Error", "Motor Over Temp", "Reserved", "Reserved"; Param5= "Thermal Overload", "Phase Error", "Valve Jammed", "Manual Moved", "Open Torque Switch Fault", "Close Torque Switch Fault", "Reserved", "Reserved"; Param6= "Local ESD Active", "Remote ESD Active", "Open Inhibit Active", "Close Inhibit Active", "Not in Remote", "Move Test Active", "Reserved", "Reserved"; Param7= "Discrete Input #1", "Discrete Input #2", "Discrete Input #3", "Discrete Input #4", "Discrete Input #5", "Discrete Input #6", "Discrete Input #7", "Discrete Input #8"; Param8= "Relay Discrete Output #1", "Relay Discrete Output #2", "Relay Discrete Output #3", "Relay Discrete Output #4", "Relay Discrete Output #5", "Relay Discrete Output #6", "Relay Discrete Output #7", "Reserved"; Param9= "Stop", "Open", "Close"; Param10= "Disable Network ESD", "Enable Network ESD"; Param11= "User Output AS-1", "User Output AS-2", "User Output AS-3", "User Output AS-4", "User Output AR-1", "User Output AR-2", "User Output AR-3", "Reserved"; Param16= "Indication of 24VDC UPS power avialable", "Low battery indication", "Flat battery indication", "Battery not installed (only until first time installed)", "Reserved", "Reserved", "Reserved", "Reserved"; Param17= "Limiguard Fault", "Interboard Communication Fault", "Interboard Power Fault", "Low Battery Indication", "Reserved", "Reserved", "Reserved", "Reserved"; Param20= "AO_Ctrl_Valve_Flow_Chan Attribute 1", "DO_Position_Chan Attribute 9", "DO_ESD_Poll_Cnxn Attribute 21", "DO_Relay_Chan Attribute 11", "DO_Move_Test_Chan Attribute 18", "AO_Analog_Output_Chan Attribute 19", "Reserved", "Reserved"; Param26= "Analog Position Transmitter (APT)", "APT Polarity (0 = high 4mA, 1 = high 20mA)", "Analog Torque Transmitter (ATT)", "ATT Polarity (0 = high 4mA, 1 = high 20mA)", "DDC Offset (0 = 0mA, 1 = 4mA)", "Unused", "Unused", "Unused", "Unused", "Scaling (0=0-100, 1=0-255, 2=0-4095, 3=Reserved)", "Scaling (0=0-100, 1=0-255, 2=0-4095, 3=Reserved)", "Unused", "Unused", "Unused", "Unused", "Unused"; Param64= "linear moving valve, sliding valve", "rotary moving valve, part-turn", "rotary moving valve, multi-turn"; Param65= "electropneumatic", "electric", "electrohydraulic", "others"; Param72= "No Action", "Open", "Close", "Stop", "Preset Position"; Param78= "Analog (Positioning Mode)", "Digital (Open/Close Mode)"; Param80= "125k", "250k", "500k"; $ Param84= $ "125k", $ "250k", $ "500k", $ PGM, PGM, PGM, PGM, PGM, PGM, PGM; Param85= "Disable", "Enable"; Param86= "Assembly Instance 105", "Assembly Instance 106", "Assembly Instance 107", "Assembly Instance 108", "Assembly Instance 109"; Param87= "Assembly Instance 100", "Assembly Instance 101", "Assembly Instance 102", "Assembly Instance 103", "Assembly Instance 104"; Param88= "Assembly Instance 106", "Assembly Instance 107", "Invalid", "Assembly Instance 109"; Param89= "Assembly Instance 105", "Assembly Instance 106", "Assembly Instance 107", "Assembly Instance 108", "Assembly Instance 109"; [Groups] $ Parameter Groups Section: $ For more information about the meaning of each entry, please check $ CIP Networks Library Volume 1 Chapter 7-3.6.6 Group1= "Channel Interface Object", $ Group Name 23, $ Number of members 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, $ List of members 11, 12, 13, 14, 15, 16, 17, 18, 19, 20, 21, 22, 23; Group2= "Transducer Block Object", $ Group Name 55, $ Number of members 24, 25, 26, 27, 28, 29, 30, 31, $ List of members 32, 33, 34, 35, 36, 37, 38, 39, 40, 41, 42, 43, 44, 45, 46, 47, 48, 49, 50, 51, 52, 53, 54, 55, 56, 57, 58, 59, 60, 61, 62, 63, 64, 65, 66, 67, 68, 69, 70, 71, 72, 73, 74, 75, 76, 77, 78; Group3= "DeviceNet Object", $ Group Name 5, $7, $ Number of members 79, 80, 81, $ List of members $ 82, 83, $ 84, 85; Group4= "Connection Object", $ Group Name 4, $ Number of members 86, 87, 88, 89; $ List of members $ End of File